Description
- A head-mounted temperature transmitter is used to convert input signals such as RTD, a thermocouple to linear output signal 4-20 mA.
Input: RTD/Thermocouple
Output signal: 4-20mA
Max load: Max. (V power supply-7.5V)/0.022A (current output)
Measurement: Tempt-linearity, resistance-linearity, voltage-linearity
Circuit limit: <= 22mA
Response time: <= 1second
Saturation current: Low side 3.9mA, high side 20.5mA
Alarm current: Sensor damager or sensor turns off the output is 3.9mA
or 22mA (Except Tc)
Accuracy: 0.1%FS
Measuring accuracy is related to measuring rang
Power supply: U=12V to 40V
Working temperature: -40 to 85℃
Storage temperature: -40 to 100℃
Condensation: Allowable
Protection: IP-66 (Mounted)
Earthquake resistance: 4g/2 to 150hz
Voltage affection: Can ignore
Mounted angle: No limit
Mount area: Top of b type box