Head Mounted Temperature Transmitter Is Used For Resistance Thermometer (RTD), Thermocouple (TC), Resistance Transmitter, Voltage (mV) Signal Input, Two Wire 4-20mA Analog Output, Mounted Inside Transmitter (Form B).

Function

  • Transfer Various Kinds Of Input Signal Into 4-20mA Output
  • Input: RTD, Thermocouple
  • Configuration By PC
  • 2 Kinds Of Resistance Thermometer Input (RTD)
  • 8 Kinds Of Thermocouple (TC)
  • Built-In Cold Junction Compensation

Installation Schematic Diagram

Appearance Structure Diagram

Wire Connection

Technical Parameter

  • Input – Resistance Temperature Detector (RTD), Thermocouple (TC), And Linear Resistance
  • Cold Junction Compensation Temperature Scope: -20∼60°C
  • Output Signal: 4-20mA
  • Output Current Of Upper And Lower Limit Overflow Alarm: IH=21mA, IL=3.8mA
  • Power Supply: 12V-40V Dc
  • Temperature Drift: 0.02%FS/°C
  • Response Time: Reach To 90% Of The Final Value For 1s
  • Used Environmental Temperature: -40∼80°C
  • Storage Temperature: -40∼100°C
  • Installation Area: B-Type Top Cassette Installation